Solution

To provide customers with power system integration solutions, with technology to lead the healthy growth of power technology, is your trusted partner.

Emergency Power System Scheme


Overview

 

  • Article 6.2.1 of GB 51348-2019 "Civil Building Electrical Design Standard (Description of Provisions)" stipulates as follows: Emergency Power Supply (Emergency Power Supply), referred to as EPS, is a power supply equipment composed of power converter, energy storage device (battery) and transfer switch (electronic or mechanical). When the AC input power is normal, the AC input power is directly output through the transfer switch.
  • The AC input power simultaneously charges the battery pack through the converter. In case of interruption (such as power interruption, voltage does not meet the power supply requirements), EPS uses the energy storage discharge of the battery pack to pass through the inverter transformation, and automatically switches to the emergency state to supply power to the load through the transfer switch. 
Lianxin Power Supply

Our advantage

01


Lianxin Power Supply

Reasonable equipment layout, good seismic resistance and sealing performance, high reliability and stability;

 


02


Lianxin Power Supply

The equipment adopts imported IPM intelligent power module assembly, good reliability and high safety;

 


03


Lianxin Power Supply

The equipment can realize fire linkage control according to user requirements, and can set a main and a standby dual power input power supply system automatic switching;


04


Change the principle, reduce weight

The equipment adopts the plug-in design process, which is flexible in assembly and convenient in debugging and installation;


05


Lianxin Power Supply

The panel adopts backlit LED liquid crystal display, with multi-channel analog, switch monitoring and protection functions, real-time display of operating status;


Technical parameters

  • Main Technical Parameters of Products
Picture Name

Model

LY S-100~1500KVA

Charger

Input mains power

AC380V(±15%)、50Hz±3%

Charging voltage

DC400V-DC1000V

Charging current

3-20A

Charging method

Automatic conversion between equalization and float charging

Storage battery

Rated voltage

DC400V-DC1000V

Backup time

≥ 90 minutes, 30, 60, 90, and 120 minutes can be selected according to demand

Charging time

< 24h

Emergency inverter

Emergency voltage

AC220/380V(±15%)、50Hz±3%

Output waveform

Sine wave (THD ≤ 5%)

Overload capacity

≤ 120% normal operation

Protection function

Protection against overcharging, short circuit in charging circuit, over discharge, overvoltage, undervoltage, etc

Emergency switching

Mechanical switching ≤ 0.25s, static electronic switching ≤ 3ms