Emergency power supply (EPS)


● 30-180min can be configured according to emergency time ● With fire linkage interface ● Imported IPM intelligent power module assembly ● With forced emergency start button and automatic/manual switch ● The panel adopts backlit LED liquid crystal display ● The charging device has the function of automatic conversion of uniform charging and floating charging


Classification:

Keywords: emergency power supply, energy storage power supply

  • Product Description
  • Technical features
  • Technical parameters
  • Selection scheme
  • Specifications and models
  • Emergency power supply is translated from English by the Emergency Power Supply, referred to as EPS, which is composed of charger, inverter, battery, isolation transformer, switch and other devices to invert DC power into AC power for emergency power supply. It can automatically switch to the backup power supply when the main power supply fails. It combines the advantages of uninterruptible power supply UPS and emergency generator set to provide reliable power guarantee in case of power failure or emergency.

    The main purpose of emergency power supply is to provide stable and reliable power for important equipment in case of power failure or emergency, so as to ensure the normal operation of equipment. It is widely used in chemical industry, pipe gallery, rail transit, highway construction and other fields to provide emergency power support for key equipment and facilities. The emergency power supply has the advantages of high efficiency, reliability, and intelligence. It can quickly switch to the backup power supply in a short time and ensure the continuity of power supply. It is one of the important equipment to ensure the normal operation of important equipment and facilities, especially in the case of power failure or emergency.

    Article 3.2.9 of the GB51348-2019 "Civil Building Electrical Design Standard" stipulates that for the especially important load in the first-class load, the power supply shall meet the following requirements: in addition to the dual power supply, emergency power supply shall be added; The emergency power supply circuit shall be self-contained and other loads shall not be connected to the emergency power supply circuit. The switching time of emergency power supply shall meet the requirements of equipment allowing interruption of power supply. Power supply time of emergency power supply, the requirements for the longest continuous operation time of electrical equipment shall be met; for the ports on the end distribution box changeover switch of the particularly important load in the first load, power monitoring and fault alarm shall be set.

  • 1, original technology: into a number of independent research and development of current and voltage PI acquisition technology, as well as BAS and FAS linkage, to ensure the stability and safety of the system.

    2. Module plugging and unplugging: with unique modular design, each module can be quickly plugged and interchanged, which is convenient for system testing, operation and maintenance, and improves operation efficiency.

    3. Fast switching: through PI acquisition, the mains power is quickly switched to the emergency standby power supply within 5 milliseconds to ensure the rapid and stable power supply of load equipment.

    4. Intelligent monitoring: With advanced intelligent monitoring function, it can monitor the power supply running status in real time, provide users with accurate running data, and facilitate the maintenance of the power supply system.

  • Model LY S-1.5~1500KVA
    Charger Input mains AC380V(±15%)、50Hz±3%
    Charging voltage DC400V-DC1000V
    Charging current 3-20A
    Charging mode Automatic conversion of even charge and floating charge
    Battery Rated voltage DC400V-DC1000V
    Standby time ≥ 90min, 30, 60, 90, 120min can be selected according to requirements
    Charging time < 24h
    Emergency Inverter Emergency voltage AC220/380V(±15%)、50Hz±3%
    Output waveform Sine wave (THD ≤ 5%)
    Overload capacity ≤ 120% normal operation
    Protection function Overcharge, charging circuit short circuit, over discharge, overvoltage, undervoltage and other protection
    Emergency switching Mechanical switching ≤ 0.25s, static electronic switching ≤ 3ms
    Noise Emergency ≤ 60dB
  • Lighting EPS power supply device

    ·The rated output power shall not be less than 1.3 times the total capacity of the connected emergency lighting load.

    Electric power equipment EPS power supply device

    ·When the EPS power supply unit has multiple motors and all start

    EPS capacity = 1.05 × (the sum of the motor power directly started × the sum of the motor power started by 5 stars and triangle × 3 the motor power value started by variable frequency × 1.1)

    · When the EPS power supply unit has multiple motors and they are not started at the same time

    EPS capacity = 1.05 × (the sum of the power of each motor, the power of the single motor with the largest direct starting capacity, X7 stars, the power of the single motor with the largest triangular starting capacity, × 3 the power of the motor with the largest variable frequency starting capacity, × 1.1)

    The above motor work must also meet the following conditions:

    a) The maximum single motor power for direct start is less than 1/7 of the EPS usable capacity;

    B) The maximum power of a single motor for star-delta starting is less than 1/3 of the usable capacity of EPS;

    c) The maximum single motor power for variable frequency start is less than 9/10 of the EPS usable capacity;

    d) Adjust the capacity of EPS according to the maximum number in the above conditions to meet the working conditions of the motor. At the same time, the starting sequence of the motor shall be the first to start directly, followed by the star-delta starting, and finally the variable frequency starting.

  • Classification Specifications Outline and size of main cabinet
    Width * Depth * Height (mm)
    Battery cabinet dimensions
    Width * Depth * Height (mm)
    Emergency time
    (Standard)
    Single cabinet weight
    (including battery) Kg
    Model Rated power
    (KVA)
    Small LY-D 1.5-3 800*600*2200 / 90min 1200
    3.5-5 800*600*2200 / 90min 1200
    5.5-8 800*600*2200 800*600*2200 90min 1200
    8.5-10 800*600*2200 800*600*2200 90min 1200
    10-15 800*600*2200 800*600*2200 90min 1200
    16-20 800*600*2200 800*600*2200 90min 1200
    20-50 800*600*2200 800*600*2200*2 90min 1200
    Medium LY-S 50-100 800*600*2200 800*600*2200*3 90min 1200
    110-200 800*600*2200 800*600*2200*4 90min 1200
    220-300 800*800*2200 800*600*2200*6 90min 1200
    Large 310-400 1000*1000*2200 1000*600*2200*8 90min 1200
    410-500 1000*1000*2200 1000*600*2200*10 90min 1200
    600-750 1000*1000*2200 1000*600*2200*12 90min 1200
    800-1000 1000*1000*2200 1000*600*2200*15 90min 1200
    1200-1500 1000*1000*2200 1000*600*2200*20 90min 1200